If you have many lights, a capacity test may cause errors even though the Lights are faultless.
The test start for all Lights generates a high level of wireless traffic. During test startup, some messages may not arrive on time, so the system will time out in the log and display an error. This can be prevented by making the test start for around 100 lights via the timer. This reduces wireless traffic and allows all messages to arrive on time.
The distances between the individual timers should always be one hour after the completion of the last endurance check.
By default the number of programmable timers is limited to 5 and can be extended by activation. For further information about system expansion, please contact your Distributor.
As an example for a 3 hour test:
A limited time period of maximum one week must be chosen in the schedule, otherwise the duration test will be repeated every week:
This procedure is necessary up to software version 2.3.2.
For subsequent versions, the above procedure is solved via an automatic schedule of the software.